Brand: URANUSOrigin: TurkeyCategory: Fire Resistant Cables

URANUS BMUR120E30

Fire resistant cable to BS 7629-1:2015: silicone insulation, tinned copper drain wire plus AL-PE foil, 300/500 V. Certified by LPCB.

URANUS BMUR120E30 is a halogen-free, flame-retardant, low-smoke fire resistant cable to BS 7629-1:2015 with an EN 50200 Annex E (30 min water option) rating. Screened with tinned copper drain wire and aluminium foil, certified by LPCB.

Approvals

LPCB

From Falcon's approvals register. View register

Need this product?

Send quantities, sizes and your required date. We reply with availability and pricing.

Features and advantages

  • Flexible — very flexible construction that makes installation easier in all conditions
  • LSZH (low smoke zero halogen) — very low toxicity, low smoke emission and no corrosive gas, safeguarding human life and electronic equipment
  • Flame retardant — limits the spread of fire along the cable run
  • Protected against electrostatic noise — fully screened, with twisted conductors
  • Moisture resistant — no special terminals needed to prevent moisture absorption; can be installed in damp environments
  • Suitable for data transmission — twisted conductors give clear transmission

Applications

  • Machines and equipment that must keep working during a fire (emergency elevators, fire water pumps)
  • Ventilation systems connected to the fire alarm system
  • Emergency lighting at fire escape exits
  • Emergency power supplies
  • Places where human life and valuable materials and equipment need to be protected

Technical specifications

Construction
PropertyValue
ConductorElectrolytic solid copper wire (IEC 60228 / DIN EN 60228 / EN 60228 Class 1)
InsulationEN 50363-1 EI2 silicone compound
Core identificationHD 308 S2 (see colour code)
Lay-upCores stranded in layers
Overall screenTinned copper drain wire + aluminium foil (AL-PE)
SheathHalogen-free flame-retardant compound (HFFR, BS 7655-6.1 LT53)
Sheath colourRed (RAL 3000) or white (RAL 9003)
Reference standardBS 7629-1:2015
Technical properties
PropertyValue
Operating voltage300/500 V
Test voltage2 kV
Insulation resistancemin. 100 MΩ × km
Temperature rangeOperation: −40 °C to +70 °C
Min. bending radiusOperation: 6 × cable diameter
Flame resistant testIEC 60332-1-2, VDE 0482-332-1-2, EN 60332-1-2
Flame propagation test (Cat A)IEC 60332-3-22, VDE 0482-332-3-22, EN 60332-3-22
Smoke density testIEC 61034-2, VDE 0482-1034-2, EN 61034-2
Halogen-free testIEC 60754-1, VDE 0482-267-2-1, EN 50267-2-1
Corrosive gas testIEC 60754-2, VDE 0482-267-2-3, EN 50267-2-3
Circuit integrity with shock and water (C, W, Z)BS 6387:2013
Circuit integrity test (FE180)IEC 60331-21
Circuit integrity with shock test (PH120)EN 50200; VDE 0482-200; BS EN 50200
Circuit integrity with shock test (water option, 30 min)EN 50200 + Annex E; VDE 0482-200 + Annex E; BS EN 50200 + Annex E
Dimensions, resistance and current load
Cross sectionApprox. overall diameter (mm, ±10%)Insulation resistance (MΩ/km)Conductor resistance (Ω/km)Conductor loop resistance (Ω/km)Drain wire resistance (Ω/km)Current load (A)
2 × 1 mm²6.9010018.136.21 mm² = 18.216
2 × 1.5 mm²7.9010012.1024.201.5 mm² = 12.220
3 × 1.5 mm²8.2010012.1024.201.5 mm² = 12.220
4 × 1.5 mm²9.2010012.1024.201.5 mm² = 12.220
2 × 2.5 mm²9.301007.415.12.5 mm² = 7.5625
3 × 2.5 mm²11.001007.415.12.5 mm² = 7.5625
4 × 2.5 mm²10.801007.415.12.5 mm² = 7.5625
2 × 4 mm²10.301004.619.204 mm² = 4.724
3 × 4 mm²10.401004.619.204 mm² = 4.724
4 × 4 mm²12.101004.619.204 mm² = 4.724
Core colour code (HD 308 S2)
CoresColours
2 coreBlue, brown
3 coreBrown, black, grey
4 coreBlue, brown, black, grey
Applicable standards
Standard
BS 7629-1:2015
BS 6387:2013 (Category CWZ)
EN 50200:2015 Annex E (30 min)
BS 5839-1:2013 (Clause 26.2d standard)
EN 60754-2:2014
EN 60332-3-22:2009
Typical applications — design standards
StandardScope
BS 5839-1Fire detection and fire alarm systems for buildings — code of practice for design, installation, commissioning and maintenance of systems in non-domestic premises
BS 5839-8Fire detection and fire alarm systems for buildings — code of practice for design, installation, commissioning and maintenance of voice alarm systems
BS 5839-9Fire detection and fire alarm systems for buildings — code of practice for design, installation, commissioning and maintenance of fire detection and fire alarm systems in domestic premises
BS 5266-1Emergency lighting — code of practice for the emergency lighting of premises
BS 8519Selection and installation of fire-resistant power and control cable systems for life safety and fire-fighting applications